Mastering Your Power: A Hands-On Guide to Programming the Rish Master 3428/3430 Multi-Function Meter

 

We live in a world driven by efficiency. Whether you manage a large industrial plant or oversee a commercial building, understanding your electrical consumption is key to saving money and improving operations. Gone are the days of relying on a dozen different analog meters. Today, the modern workhorse of electrical monitoring is the Multi-Function Meter (MFM)—a powerhouse of digital measurement neatly packaged into a compact device.

The Digital Heart of Your Electrical Panel

Table of Contents

A Multi-Function Meter is essentially the digital brain of your electrical panel. It takes the messy reality of electrical flow—the fluctuating voltages, currents, and power variations—and turns it into clean, usable data.

These instruments measure every critical electrical parameter you could need:

  • Voltage (V) & Current (A)
  • Active Power (kW), Reactive Power (kVAr), & Apparent Power (kVA)
  • Energy (kWh, kVArh, kVAh)
  • Frequency (Hz)
  • Power Factor (PF)
  • Harmonic Distortions (THD)

But a meter is only as good as its setup. That’s where the Rish Master 3428 / 3430 models come in. Manufactured by Rishabh Instruments Pvt. Ltd., these meters are celebrated for being field programmable and exceptionally user-friendly. You don't need a laptop or special software to get them running; everything can be done right from the front panel interface.

If you're installing a new meter, replacing an old one, or just trying to troubleshoot a discrepancy, you need to know how to properly program it. A poorly configured meter is worse than no meter at all, giving you misleading data that can cost you dearly.


The Essential Configuration Checklist: Why Programming Matters

Before your Rish Master 3428 or 3430 can provide a single accurate measurement, it needs to be told exactly what it is connected to. It needs to know the "rules of the game" for your specific site.

The core parameters you must configure are:

Parameter What it Does Why it's Critical
System Type Defines your electrical network (e.g., 3-Phase 4-Wire, 3-Phase 3-Wire, or 1-Phase 2-Wire). Incorrect selection will lead to completely wrong power and energy readings.
CT Primary Value The primary rating of your Current Transformer (e.g., 100A, 400A). This scale factor allows the meter to calculate the real current from the small secondary current.
CT Primary Value The primary rating of your Current Transformer (e.g., 100A, 400A). This scale factor allows the meter to calculate the real current from the small secondary current.
CT Secondary Value The secondary rating of your CTs (typically 1A or 5A). Must match the output of the installed CTs to ensure correct current input.
PT Primary Value The primary rating of your Potential Transformer (e.g., 11kV, 415V). This scale factor allows the meter to display the actual high-side voltage.
PT Secondary Value The secondary rating of your PTs (typically 110V or 415V). Must match the voltage input terminals of the meter.

The Goal: You are essentially giving the meter its identity and context so it can correctly interpret the raw electrical signals it receives. Get these right, and your measurements are gold.


Navigating the Front Panel: Your Two Keys to Power

The front panel of the Rish Master 3428 / 3430 typically features a bright LED display and just two push buttons—the 'Up and 'Down keys. These two buttons are your only interface for both checking measurements and making deep configuration changes.

Section 1: Reviewing Your Measurements

The first job of the meter is to show you what's happening right now. In normal operating mode, a short press of the 'Up or 'Down button cycles through the live measurement screens.

1.1: Single-Phase Measurement Structure

When configured for a Single-Phase system, the scrolling sequence for measurement screens usually follows this structure:

Display Screen Parameter Displayed
Screen 1 Voltage (V) - Line to Neutral
Screen 2 Current (A) - Line Current)
Screen3 Frequency (Hz) & Power Factor (PF)
Screen 4 Active Power (kW)
Screen 5 Reactive Power (kVAr)
Screen 6 Apparent Power (kVA)
Screen 7 Total Active Energy (kWh)
Screen 8 Max/Min recorded values

1.2: Three-Phase Measurement Structure

For a 3-Phase system (which is the most common use case for these meters), the measurement menu is far more detailed, allowing you to check phase-specific values:

Display Screen Parameter Displayed
Screen 1 System Voltage (V SYS​ ) & System Current (A SYS​ )
Screen 2 Line-to-Neutral Voltages (V L1​ -N, VL2​ -N, V L3​ -N)
Screen3 Line-to-Line Voltages (V L1​ -L2, V L2​ -L3, V L3​ -L1)
Screen 4 Line Currents (A L1​ , A L2​ , A L3​ )
Screen 5 Neutral Current (A N​ ) and System Power Factor (PF SYS​ )
Screen 6 System Power (kW SYS​ , kVAr SYS​ , kVASYS​ )
Screen 7 Total Import Active Energy (kWhImport​ )
Screen 8 Total Export Active Energy (kWh Export​ )
Screen 9 System Total Harmonic Distortion (THD)

Remember: Use the and keys for quick scrolling through these measurement values.


Section 2: Entering the Configuration Mode (The 'Setup' Menu)

Now for the part that requires a little more care: configuring the meter. Accessing the setup menu is the first critical step and typically involves a simultaneous button press to prevent accidental changes.

Step 2.1: Accessing the Programming Mode

To enter the programming mode (the "Setup" menu) on the Rish Master 3428/3430:

  1. Simultaneously press and hold the Up Arrow and Down Arrow keys for approximately 5 seconds.
  2. The display will likely flash 'PASS' or 'CODE', prompting you for the password.

Step 2.2: Entering the Password

If no password was previously set (the default is often 0000):

  1. Use the Down Arrow key to scroll through the digits (0-9).
  2. Use the Up Arrow key to confirm the digit and move to the next position.
  3. Once the correct 4-digit password (e.g., 0000) is entered, press the Up Arrow key again to confirm and enter the main configuration menu, which often displays 'Set UP' or the first menu item.

Step 2.3: The Configuration Menu Structure

The configuration menu is where you set the essential parameters mentioned earlier. It’s structured logically to walk you through the settings.

Menu Item Action / Function
Sys System Type Selection: Set to 3P4W (3-Phase 4-Wire) or 3P3W (3-Phase 3-Wire). This is the most critical setting.
Up PT Primary Value: Enter the high-side voltage of your Potential Transformer (e.g., 11000V).
Us PT Secondary Value: Enter the low-side voltage connected to the meter (e.g., 110V).
Ap CT Primary Value: Enter the full-load current of your Current Transformer (e.g., 400A).
As CT Secondary Value: Set the output current of your CTs (5A or 1A).
Auto Auto-Scrolling: Enable or disable the automatic cycling of measurement screens.
cN Low Current Cutoff: Suppress readings below a certain current (e.g., 30mA) to eliminate noise.
Addr RS485 Modbus Address: If using communication, set the unique device ID (1-247).
PUL Pulse Output Configuration: Set the energy type and pulse rate for relay outputs (if applicable).
rSEt Reset Energy: Reset the stored kWh, kVArh, and kVAh values to zero. Use with caution!

Step 2.4: Executing the Configuration Change

To change a value (e.g., the CT Primary):

  1. Scroll through the menu using the Up Arrow and Down Arrow keys until the display shows 'AP'.
  2. Press the Up Arrow key (or sometimes the Down Arrow key, depending on the exact model’s logic) to enter edit mode for that parameter.
  3. The first digit will start flashing. Use the Down Arrow key to scroll the value of the flashing digit from 0 to 9.
  4. Use the Up Arrow key to accept the digit and move to the next position.
  5. Repeat the scroll/confirm process until the full value is entered.
  6. Once the value is correct, press the Up Arrow key one final time to confirm and exit the edit screen, returning to the main setup menu.
  7. Crucially, repeat this for all required parameters (especially PT/CT Ratios and System Type).
  8. Finally, scroll to the 'SAVE' or 'End' option and confirm to save your settings. The meter will reboot or return to the main measurement screen, applying the new configuration.

Final Thoughts: The Value of Precision Monitoring

The Rish Master 3428 and 3430 are robust, reliable meters designed for the real world. Their simple front-panel programming is a huge advantage, allowing electricians and technicians to quickly commission them without specialized equipment.

By diligently setting the System Type and the CT/PT Ratios, you ensure that the meter is not just reading numbers, but is providing accurate, actionable intelligence about your power usage. This precision is what enables effective energy management, cost savings, and a clearer understanding of your electrical network's health. Taking a few minutes to master the front panel interface gives you complete control over your power story.

To see a practical demonstration of programming a similar Rishabh multi-function meter, check out this video: Rish LM1360 MFM PROGRAMMING, SETTING CONFIGURATION IN HINDI. This video is relevant as it provides a visual guide and process for programming a different, but similar, model of Rishabh multi-function meter.


Detailed manual can be downloaded from this link 